Model | LGH-15RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.44-0.46 | 0.37-0.38 | 0.25-0.25 | 0.14-0.15 | |
Power Consumption(W) | 96-100 | 80-90 | 53-59 | 30-35 | |
Air Volume | (m3/h) | 150 | 150 | 110 | 70 |
(L/s) | 42 | 42 | 31 | 19 | |
External static pressure | mmH2O | 10.2-10.7 | 6.6-7.1 | 3.6-4.1 | 1.4 |
(Pa) | 100-105 | 65-70 | 35-40 | 14 | |
Temperature exchange efficiency (%) | 82 | 82 | 84 | 85.5 | |
Enthalpy exchange efficiency | Heating | 75 | 75 | 77.5 | 81 |
Cooling | 73 | 73 | 76.5 | 81 | |
Noise(dB) | (Measured at 1.5m under the center | 27.5-28 | 26.5-27 | 22-23.5 | 18 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 273 x 735 x 780 | ||||
Starting Current | Under 0.8A Less |
Model | LGH-15RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.45-0.46 | 0.37-0.38 | 0.25-0.26 | 0.14-0.15 | |
Power Consumption(W) | 97-110 | 81-91 | 54-61 | 30-35 | |
Air Volume | (m3/h) | 150 | 150 | 110 | 70 |
(L/s) | 42 | 42 | 31 | 19 | |
External static pressure | mmH2O | 10.2-10.7 | 6.6-7.1 | 3.6-4.1 | 1.4 |
(Pa) | 100-105 | 65-70 | 35-40 | 14 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 28.5-29 | 27-28 | 23-24 | 18-19 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 273 x 735 x 780 | ||||
Starting Current | Under 0.8A Less |
Model | LGH-25RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.52-0.55 | 0.47-0.48 | 0.26-0.27 | 0.17-0.18 | |
Power Consumption(W) | 113-129 | 102-114 | 56-62 | 36-42 | |
Air Volume | (m3/h) | 250 | 250 | 155 | 105 |
(L/s) | 69 | 69 | 43 | 29 | |
External static pressure | mmH2O | 8.2-8.7 | 5.1-6.1 | 2-2.5 | 0.9 |
(Pa) | 80-85 | 50-60 | 20-25 | 9 | |
Temperature exchange efficiency (%) | 79 | 79 | 81.5 | 83.5 | |
Enthalpy exchange efficiency | Heating | 69.5 | 69.5 | 74 | 77.5 |
Cooling | 68 | 68 | 72.5 | 76 | |
Noise(dB) | (Measured at 1.5m under the center | 26-27 | 25-26 | 20-21.5 | 18-19 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 273 x 735 x 780 | ||||
Starting Current | Under 0.8A Less |
Â
Model | LGH-25RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.53-0.55 | 0.47-0.48 | 0.26-0.27 | 0.17-0.18 | |
Power Consumption(W) | 115-131 | 103-115 | 56-63 | 36-42 | |
Air Volume | (m3/h) | 250 | 250 | 155 | 105 |
(L/s) | 69 | 69 | 43 | 29 | |
External static pressure | mmH2O | 8.2-8.7 | 5.1-6.1 | 2-2.5 | 0.9 |
(Pa) | 80-85 | 50-60 | 20-25 | 9 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 26.5-27.5 | 25.5-26.5 | 20.5-22 | 18-19 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 273 x 735 x 780 | ||||
Starting Current | Under 0.8A Less |
Model | LGH-35RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.92-0.92 | 0.74-0.74 | 0.5-0.51 | 0.28-0.3 | |
Power Consumption(W) | 195-212 | 160-169 | 105-116 | 58-69 | |
Air Volume | (m3/h) | 350 | 350 | 210 | 115 |
(L/s) | 97 | 97 | 58 | 32 | |
External static pressure | mmH2O | 15.8-16.3 | 7.6-8.2 | 2.5-3.1 | 0.9 |
(Pa) | 155-160 | 75-80 | 25-30 | 9 | |
Temperature exchange efficiency (%) | 80 | 80 | 85 | 88 | |
Enthalpy exchange efficiency | Heating | 71.5 | 71.5 | 76.5 | 81.5 |
Cooling | 71 | 71 | 75.5 | 81 | |
Noise(dB) | (Measured at 1.5m under the center | 32-32 | 28.5-29.5 | 21.5-23 | 18 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 315 x 874 x 888 | ||||
Starting Current | Under 2.4A Less |
Model | LGH-35RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 0.93-0.94 | 0.77-0.77 | 0.51-0.52 | 0.28-0.3 | |
Power Consumption(W) | 197-217 | 164-173 | 105-116 | 58-69 | |
Air Volume | (m3/h) | 350 | 350 | 210 | 115 |
(L/s) | 97 | 97 | 58 | 32 | |
External static pressure | mmH2O | 15.8-16.3 | 7.6-8.2 | 2.5-3.1 | 0.9 |
(Pa) | 155-160 | 75-80 | 25-30 | 9 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 32.5-32.5 | 29.5-30.5 | 21.5-24 | 18 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 20 | ||||
External Dimesion (H x W x D) (mm) | 315 x 874 x 888 | ||||
Starting Current | Under 2.4A Less |
Model | LGH-50RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.2-1.25 | 1.0-1.0 | 0.85-0.85 | 0.4-0.4 | |
Power Consumption(W) | 255-286 | 207-228 | 175-190 | 80-95 | |
Air Volume | (m3/h) | 500 | 500 | 390 | 180 |
(L/s) | 139 | 139 | 108 | 50 | |
External static pressure | mmH2O | 15.3-15.8 | 6.6-9.2 | 4.1-6.1 | 1 |
(Pa) | 150-155 | 65-90 | 40-60 | 10 | |
Temperature exchange efficiency (%) | 78 | 78 | 81 | 86 | |
Enthalpy exchange efficiency | Heating | 69 | 69 | 71 | 78 |
Cooling | 66.5 | 66.5 | 68 | 77 | |
Noise(dB) | (Measured at 1.5m under the center | 33-34 | 30.5-32 | 26.5-28 | 19 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 32 | ||||
External Dimesion (H x W x D) (mm) | 315 x 1016 x 888 | ||||
Starting Current | Under 3.0A Less |
Model | LGH-50RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.25-1.25 | 1.0-1.0 | 0.85-0.85 | 0.4-0.4 | |
Power Consumption(W) | 260-290 | 210-230 | 180-195 | 80-95 | |
Air Volume | (m3/h) | 500 | 500 | 390 | 180 |
(L/s) | 139 | 139 | 108 | 50 | |
External static pressure | mmH2O | 15.3-15.8 | 6.6-9.2 | 4.1-6.1 | 1 |
(Pa) | 150-155 | 65-90 | 40-60 | 10 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 34-35 | 31-32.5 | 27-29 | 19 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 32 | ||||
External Dimesion (H x W x D) (mm) | 315 x 1016 x 888 | ||||
Starting Current | Under 3.0A Less |
Model | LGH-65RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.7-1.8 | 1.5-1.5 | 1.2-1.2 | 0.6-0.6 | |
Power Consumption(W) | 350-380 | 308-322 | 248-265 | 120-140 | |
Air Volume | (m3/h) | 650 | 650 | 520 | 265 |
(L/s) | 181 | 181 | 144 | 74 | |
External static pressure | mmH2O | 11.2-12.2 | 6.1-8.2 | 4.1-5.1 | 0.8 |
(Pa) | 110-120 | 60-80 | 40-50 | 8 | |
Temperature exchange efficiency (%) | 77 | 77 | 80 | 86 | |
Enthalpy exchange efficiency | Heating | 68.5 | 68.5 | 70.5 | 78 |
Cooling | 66 | 66 | 68.5 | 77 | |
Noise(dB) | (Measured at 1.5m under the center | 34-34.5 | 32-33 | 28.5-31.5 | 22 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 40 | ||||
External Dimesion (H x W x D) (mm) | 389 x 954 x 908 | ||||
Starting Current | Under 4.4A Less |
Model | LGH-65RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.7-1.8 | 1.5-1.5 | 1.2-1.2 | 0.6-0.6 | |
Power Consumption(W) | 350-385 | 310-335 | 250-265 | 120-140 | |
Air Volume | (m3/h) | 650 | 650 | 520 | 265 |
(L/s) | 181 | 181 | 144 | 74 | |
External static pressure | mmH2O | 11.2-12.2 | 6.1-8.2 | 4.1-5.1 | 0.8 |
(Pa) | 110-120 | 60-80 | 40-50 | 8 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 34.5-35 | 32.5-33.5 | 28.5-30.5 | 22-22.5 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 40 | ||||
External Dimesion (H x W x D) (mm) | 389 x 954 x 908 | ||||
Starting Current | Under 4.4A Less |
Model | LGH-80RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.75-1.75 | 1.6-1.6 | 1.45-1.45 | 0.60-0.65 | |
Power Consumption(W) | 380-415 | 345-370 | 315-340 | 125-145 | |
Air Volume | (m3/h) | 800 | 800 | 700 | 355 |
(L/s) | 222 | 222 | 194 | 99 | |
External static pressure | mmH2O | 14.8-15.3 | 10.7-12.2 | 8.2-9.7 | 2 |
(Pa) | 145-150 | 105-120 | 80-95 | 20 | |
Temperature exchange efficiency (%) | 79 | 79 | 80.5 | 87.5 | |
Enthalpy exchange efficiency | Heating | 71 | 71 | 72.5 | 79.5 |
Cooling | 70 | 70 | 71.5 | 79.5 | |
Noise(dB) | (Measured at 1.5m under the center | 33.5-34.5 | 32-33 | 30-31 | 22 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 53 | ||||
External Dimesion (H x W x D) (mm) | 399 x 1004 x 1144 | ||||
Starting Current | Under 3.8A Less |
Model | LGH-80RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 1.75-1.75 | 1.6-1.6 | 1.45-1.45 | 0.60-0.65 | |
Power Consumption(W) | 380-415 | 345-370 | 315-340 | 120-145 | |
Air Volume | (m3/h) | 800 | 800 | 700 | 355 |
(L/s) | 222 | 222 | 194 | 99 | |
External static pressure | mmH2O | 14.8-15.3 | 10.7-12.2 | 8.2-9.7 | 2 |
(Pa) | 145-150 | 105-120 | 80-95 | 20 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 34.5-35.5 | 33-34 | 31-32 | 22 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 53 | ||||
External Dimesion (H x W x D) (mm) | 399 x 1004 x 1144 | ||||
Starting Current | Under 3.8A Less |
Â
Model | LGH-100RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 2.3-2.4 | 2.1-2.1 | 1.7-1.7 | 0.9-0.9 | |
Power Consumption(W) | 500-535 | 445-475 | 350-380 | 175-200 | |
Air Volume | (m3/h) | 1000 | 1000 | 755 | 415 |
(L/s) | 278 | 278 | 210 | 115 | |
External static pressure | mmH2O | 16.3-17.3 | 10.2-11.2 | 5.6-6.1 | 1.8 |
(Pa) | 160-170 | 100-110 | 55-60 | 18 | |
Temperature exchange efficiency (%) | 80 | 80 | 83 | 87 | |
Enthalpy exchange efficiency | Heating | 72.5 | 72.5 | 74 | 80 |
Cooling | 71 | 71 | 73 | 79 | |
Noise(dB) | (Measured at 1.5m under the center | 36-37 | 34-35 | 31-32.5 | 21-22 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 59 | ||||
External Dimesion (H x W x D) (mm) | 399 x 1231 x 1144 | ||||
Starting Current | Under 4.6A Less |
Model | LGH-100RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | By-pass ventilation | ||||
Fan Speed | Extra High | High | Low | Extra Low | |
Current(A) | 2.3-2.4 | 2.1-2.1 | 1.7-1.7 | 0.9-0.9 | |
Power Consumption(W) | 510-550 | 460-485 | 365-395 | 175-200 | |
Air Volume | (m3/h) | 1000 | 1000 | 755 | 415 |
(L/s) | 278 | 278 | 210 | 115 | |
External static pressure | mmH2O | 16.3-17.3 | 10.2-11.2 | 5.6-6.1 | 1.8 |
(Pa) | 160-170 | 100-110 | 55-60 | 18 | |
Temperature exchange efficiency (%) | – | – | – | – | |
Enthalpy exchange efficiency | Heating | – | – | – | – |
Cooling | – | – | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 37-38 | 35-36 | 32-33 | 21-22 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 59 | ||||
External Dimesion (H x W x D) (mm) | 399 x 1231 x 1144 | ||||
Starting Current | Under 4.6A Less |
Model | LGH-150RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra High | |
Current(A) | 3.5-3.5 | 3.2-3.2 | 2.9-2.9 | 3.5-3.5 | |
Power Consumption(W) | 760-830 | 690-740 | 630-680 | 765-835 | |
Air Volume | (m3/h) | 1500 | 1500 | 1300 | 1500 |
(L/s) | 417 | 417 | 361 | 417 | |
External static pressure | mmH2O | 16.3-17.8 | 13.3-13.8 | 9.7-10.2 | 16.3-17.8 |
(Pa) | 160-175 | 130-135 | 95-100 | 160-175 | |
Temperature exchange efficiency (%) | 80 | 80 | 81 | – | |
Enthalpy exchange efficiency | Heating | 72 | 72 | 72.5 | – |
Cooling | 70.5 | 70.5 | 71.5 | – | |
Noise(dB) | (Measured at 1.5m under the center | 38-39 | 36-37.5 | 33.5-35 | 39-40.5 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 105 | ||||
External Dimesion (H x W x D) (mm) | 798 x 1004 x 1144 | ||||
Starting Current | Under 7.3A Less |
Model | LGH-150RX5-E | ||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||
Ventilation mode | By-pass ventilation | ||
Fan Speed | High | Low | |
Current(A) | 3.2-3.2 | 2.9-2.9 | |
Power Consumption(W) | 695-745 | 635-685 | |
Air Volume | (m3/h) | 1500 | 1300 |
(L/s) | 417 | 361 | |
External static pressure | mmH2O | 13.3-13.8 | 9.7-10.2 |
(Pa) | 130-135 | 95-100 | |
Temperature exchange efficiency (%) | – | – | |
Enthalpy exchange efficiency | Heating | – | – |
Cooling | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 37.5-39 | 35.5-37 |
of panel in an anechoeic chamber) | |||
Weight(kg) | 105 | ||
External Dimesion (H x W x D) (mm) | 798 x 1004 x 1144 | ||
Starting Current | Under 7.3A Less |
Model | LGH-200RX5-E | ||||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||||
Ventilation mode | LOSSNAY ventilation | ||||
Fan Speed | Extra High | High | Low | Extra High | |
Current(A) | 4.8-4.8 | 4.2-4.2 | 3.4-3.4 | 4.8-4.8 | |
Power Consumption(W) | 1035-1100 | 910-980 | 715-785 | 1040-1110 | |
Air Volume | (m3/h) | 2000 | 2000 | 1580 | 2000 |
(L/s) | 556 | 556 | 439 | 556 | |
External static pressure | mmH2O | 16.3-16.8 | 10.2-10.7 | 6.1-6.6 | 16.3-16.8 |
(Pa) | 160-165 | 100-105 | 60-65 | 160-165 | |
Temperature exchange efficiency (%) | 80 | 80 | 83 | – | |
Enthalpy exchange efficiency | Heating | 72.5 | 72.5 | 73.5 | – |
Cooling | 71 | 71 | 72 | – | |
Noise(dB) | (Measured at 1.5m under the center | 39.5-40 | 37-38 | 32.5-34 | 40.5-41 |
of panel in an anechoeic chamber) | |||||
Weight(kg) | 118 | ||||
External Dimesion (H x W x D) (mm) | 798 x 1231 x 1144 | ||||
Starting Current | Under 11.9A Less |
Model | LGH-200RX5-E | ||
Frequency/Power Source | 50Hz/Single Phase 220-240V | ||
Ventilation mode | By-pass ventilation | ||
Fan Speed | High | Low | |
Current(A) | 4.2-4.2 | 3.4-3.4 | |
Power Consumption(W) | 915-980 | 720-785 | |
Air Volume | (m3/h) | 2000 | 1580 |
(L/s) | 556 | 439 | |
External static pressure | mmH2O | 10.2-10.7 | 6.1-6.6 |
(Pa) | 100-105 | 60-65 | |
Temperature exchange efficiency (%) | – | – | |
Enthalpy exchange efficiency | Heating | – | – |
Cooling | – | – | |
Noise(dB) | (Measured at 1.5m under the center | 38-39 | 33.5-35 |
of panel in an anechoeic chamber) | |||
Weight(kg) | 118 | ||
External Dimesion (H x W x D) (mm) | 798 x 1231 x 1144 | ||
Starting Current | Under 11.9A Less |