Model |
LGH-200RX5-E |
Frequency/Power Source |
50Hz/Single Phase 220-240V |
Ventilation mode |
LOSSNAY ventilation |
Fan Speed |
Extra High |
High |
Low |
Extra High |
Current(A) |
4.8-4.8 |
4.2-4.2 |
3.4-3.4 |
4.8-4.8 |
Power Consumption(W) |
1035-1100 |
910-980 |
715-785 |
1040-1110 |
Air Volume |
(m3/h) |
2000 |
2000 |
1580 |
2000 |
(L/s) |
556 |
556 |
439 |
556 |
External static pressure |
mmH2O |
16.3-16.8 |
10.2-10.7 |
6.1-6.6 |
16.3-16.8 |
(Pa) |
160-165 |
100-105 |
60-65 |
160-165 |
Temperature exchange efficiency (%) |
80 |
80 |
83 |
– |
Enthalpy exchange efficiency |
Heating |
72.5 |
72.5 |
73.5 |
– |
Cooling |
71 |
71 |
72 |
– |
Noise(dB) |
(Measured at 1.5m under the center |
39.5-40 |
37-38 |
32.5-34 |
40.5-41 |
of panel in an anechoeic chamber) |
Weight(kg) |
118 |
External Dimesion (H x W x D) (mm) |
798 x 1231 x 1144 |
Starting Current |
Under 11.9A Less |