ModelGUF-50RD4
Power Source1-phase 220-240V 50Hz
Cooling Capacity *1kW5.57    <1.94>
Figure in <> is the recovery *1kcal/h4800    <1650>
Capacity by LOSSNAY core *1BTU/h19000    <6600>
 Power input   *3kW235-265
 Current Input   *3A1.15
Heating Capacity *2kW6.21    <2.04>
Figure in <> is the recovery *2kcal/h5340    <1750>
Capacity by LOSSNAY core *2BTU/h21200    <7000>
 Power input   *3kW235-265
 Current Input   *3A1.15
Capacity equivalent to indoor unitP32
Humidifying capacitykg/h
lbs/h
 Humidifier
External finishGalvanized, with grey insulation sheet
External dimension H x W x Dmm317x1016x1288
in.12-1/2x40x50-3/4
Net weightkg(lbs)48(106)
Heat
exchanger
LOSSNAY corePartition, Cross-flow structure, Special preserved paper-plate
Refrigerant coilCross fin(Aluminium fin and copper tube)
FANType x QuantitySA: Centrifugal fan (Sirocco fan) x 1
EA: Centrifugal fan (Sirocco fan) x 1
External
static press.   *4
Pa140
mmH2O14.3
Motor typeTotally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units
Driving mechanismDirect-driven by motor
Airflow rate
High value
m3/h500
L/s139
cfm294
Sound pressure level(Low-High)
(measured in anechoic room)    *3
db33.5-34.5
Insulation materialPolyester sheet
Air filterSupplying airNon-woven fabrics filter(Gravitational method 82%) & Optional part: High efficiency filter(Colorimetric method 65%)
Exhausting airNon-woven fabrics filter(Gravitational method 82%)
Protection deviceFuse
Refrigerant control deviceLEV
Diameter of
refrigerant pipe
Liquidmm(in.)6.35(1/4)Flare
Gasmm(in.)12.7(1/2)Flare
Connectable outdoor unitR410A CITY MULTI