Power Source |
1-Phase 220-240V 50Hz |
Cooling Capacity *1 |
kW |
11.44 <4.12> |
Figure in <> is the recovery *1 |
kcal/h |
9800 <3500> |
Capacity by LOSSNAY core *1 |
BTU/h |
39000 <14000> |
|
Power input *3 |
kW |
480-505 |
|
Current Input *3 |
A |
2.20 |
Heating Capacity *2 |
kW |
12.56 <4.26> |
Figure in <> is the recovery *2 |
kcal/h |
10800 <3650> |
Capacity by LOSSNAY core *2 |
BTU/h |
42850 <14450> |
|
Power input *3 |
kW |
480-505 |
|
Current Input *3 |
A |
2.20 |
Capacity equivalent to indoor unit |
P63 |
Humidifying capacity |
kg/h |
– |
lbs/h |
– |
|
Humidifier |
– |
External finish |
Galvanized, with grey insulation sheet |
External dimension H x W x D |
mm |
398x1231x1580 |
in. |
15-11/16×48-1/2×62-1/4 |
Net weight |
kg(lbs) |
82(181) |
Heat
exchanger |
LOSSNAY core |
Partition, Cross-flow structure, Special preserved paper-plate |
Refrigerant coil |
Cross fin(Aluminium fin and copper tube) |
FAN |
Type x Quantity |
SA: Centrifugal fan (Sirocco fan) x 1 |
EA: Centrifugal fan (Sirocco fan) x 1 |
External
static press. *4 |
Pa |
140 |
mmH2O |
14.3 |
Motor type |
Totally enclosed capacitor permanent split-phase induction motor, 4 poles, 2 units |
Driving mechanism |
Direct-driven by motor |
Airflow rate
High value |
m3/h |
1000 |
L/s |
139 |
cfm |
589 |
Sound pressure level(Low-High)
(measured in anechoic room) *3 |
db |
38-39 |
Insulation material |
Polyester sheet |
Air filter |
Supplying air |
Non-woven fabrics filter(Gravitational method 82%) & Optional part: High efficiency filter(Colorimetric method 65%) |
Exhausting air |
Non-woven fabrics filter(Gravitational method 82%) |
Protection device |
Fuse |
Refrigerant control device |
LEV |
Diameter of
refrigerant pipe |
Liquid |
mm(in.) |
9.52(3/8)Flare |
Gas |
mm(in.) |
15.88(5/8)Flare |
Connectable outdoor unit |
R410A CITY MULTI |